GCSE Physics — AQA · Electricity

The National Grid

4.2.4.3

The National Grid delivers electrical power from power stations to homes and factories. Step-up transformers raise the p.d. for the transmission cables; step-down transformers lower it to about 230 V. At the same power, a high p.d. means a small current, so less energy is wasted. Both tiers.

Loading simulation…

Symbols match your course. Open the full transformers and the national grid simulation for more presets and teacher tools.

Who needs this: every AQA student

Spec point 4.2.4.3 is for everyone: Foundation and Higher, Physics and Combined Science alike. It has no equation of its own. Instead, you explain it with two equations you must recall from 4.2.4.1, P=VIP = VI and P=I2RP = I^2R. Be ready to:

  • say what job the National Grid does
  • name its two kinds of transformer, where each one goes and what each does to the potential difference
  • explain, step by step, why sending energy at a very high p.d. wastes so little of it

How transformers work, and the transformer equations, are Higher tier and GCSE Physics only (4.7.3.4). They are on the Transformers page.

From power station to plug

The National Grid is the network that delivers electrical power to the places where it is used: homes, schools, shops and factories. Its cables hang from pylons or run underground, with transformers at each end.

  1. At the power station, step-up transformers increase the potential difference to a very high value before the energy enters the transmission cables.
  2. The cables carry the energy across the country.
  3. Near the users, step-down transformers in substations lower the p.d. in stages, until it reaches the mains value of about 230 V used at home.

Transformers only work with alternating current, and UK mains is a.c. at 50 Hz. In Britain the main lines typically run at 400 kV or 275 kV, with 132 kV lines serving regions. You do not need to learn these values.

Why the p.d. is made so high

Every cable has resistance, so the current in it heats the cable. That energy is dissipated to the surroundings and wasted. A very high p.d. keeps this loss small, through three linked steps:

  1. For the same power, P=VIP = VI shows that a higher p.d. needs a smaller current.
  2. The heating power in the cables is P=I2RP = I^2R. It depends on the current squared, so a current ten times smaller heats the cables a hundred times less.
  3. Less energy is wasted, so more of the energy sent out reaches the users. That is why the grid is efficient.

A small current has a second benefit, separate from efficiency: thinner cables can carry it without overheating, which saves money and material.

Step-down transformers then lower the p.d. because such a high value would be extremely dangerous inside buildings.

Worked example: one power, two potential differences

A power station sends 40 MW to a city through cables with a total resistance of 3.0 Ω. Compare sending it at 20 kV with sending it at 400 kV.

Given: P=40 MW=4.0×107P = 40\ \text{MW} = 4.0 \times 10^7 W, R=3.0 ΩR = 3.0\ \Omega.

Equations: I=PVI = \dfrac{P}{V}, rearranged from P=VIP = VI; then heating power =I2R= I^2R.

At 20 kV: I=4.0×10720 000=2000I = \dfrac{4.0 \times 10^7}{20\,000} = 2000 A, so the heating power is 20002×3.0=1.2×1072000^2 \times 3.0 = 1.2 \times 10^7 W, or 12 MW.

At 400 kV: I=4.0×107400 000=100I = \dfrac{4.0 \times 10^7}{400\,000} = 100 A, so the heating power is 1002×3.0=30 000100^2 \times 3.0 = 30\,000 W, or 30 kW.

Answer: at 20 kV, 12 MW of the 40 MW is wasted, so the cables transfer energy with an efficiency of only 2840=70%\dfrac{28}{40} = 70\%. At 400 kV the loss is 30 kW and the efficiency is about 99.9%. The p.d. is 20 times higher, the current is 20 times smaller and the heating is 202=40020^2 = 400 times smaller.

Try the grid yourself

In the simulation above, the transformer view loads first. Press Grid, under the stage, to open the National Grid. Its power station always sends out 100 MW, generated at 25 kV, and at first nothing steps the p.d. up.

  1. Read Current in the lines: 4000 A. Heating the lines shows 32.0 MW, so only 68.0 MW reaches the homes and three of the ten houses stay dark.
  2. Predict the current at 132 kV, then press Raise to check: 758 A, and the heating falls to 1.15 MW.
  3. Press Raise twice more, to 400 kV. The p.d. is now 16 times the generators' 25 kV, so the current is 16 times smaller (250 A) and the heating 256 times smaller (0.125 MW). The same 100 MW at each p.d. shows all four results side by side.
  4. Drag Resistance of the lines (model) to 0 Ω. Nothing is wasted at any p.d., which shows that the loss comes from the cables' resistance.

Common mistakes

  • Saying that a high p.d. makes the electricity travel faster or further. The point of the high p.d. is a small current for the same power, which means less heating of the cables.
  • Swapping the two kinds of transformer. Step-up transformers sit between the power station and the transmission cables; step-down transformers sit between the cables and the users.
  • Working out the cable loss with P = VI and the transmission p.d. That gives the total power being sent. The power wasted heating the cables is I²R, using the current in the cables and their resistance.
  • Forgetting that the current is squared in P = I²R. Halving the current cuts the heating to a quarter, not to a half.
  • Claiming that a step-up transformer adds energy or power. It raises the p.d. while the current falls, and energy cannot be created.
  • Leaving out prefixes when substituting: 132 kV is 132 000 V, and 250 MW is 250 000 000 W.

Exam-style questions

Original questions written in the style of GCSE AQA. Try each one before you reveal the answer.

  1. 1.Electricity reaches a town from a power station through the National Grid. The power station is connected to transformer X. Transmission cables run from transformer X to transformer Y, which supplies the homes in the town.

    1. (a)Name the type of transformer used at X and the type used at Y.

      2 marks
      Show the answer

      Answer: X is a step-up transformer. Y is a step-down transformer.

      Marking points

      • X: step-up (transformer)
      • Y: step-down (transformer)
    2. (b)Describe what transformer Y does. Give one reason why it is needed.

      2 marks
      Show the answer

      Answer: Transformer Y decreases the potential difference from the very high transmission value to about 230 V. A p.d. as high as the one in the transmission cables would be far too dangerous to use in homes.

      Marking points

      • It decreases the p.d. (to about 230 V / to the mains value).
      • The transmission p.d. would be (too) dangerous in homes (allow: home appliances are designed for about 230 V).
    3. (c)Most transmission cables are hung high above the ground from pylons. Suggest one reason why.

      1 mark
      Show the answer

      Answer: The cables are at a very high p.d., so they must be kept well out of reach of people and vehicles for safety.

      Marking points

      • To keep the very high p.d. cables out of reach of people (and objects), for safety (allow: cheaper than burying the cables underground).
  2. 2.An offshore wind farm sends 66 MW of electrical power to the shore along a cable. The cable has a total resistance of 2.0 Ω. The power is sent at a potential difference of 132 kV.

    1. (a)Write down the equation that links current (I), potential difference (V) and power (P).

      1 mark
      Show the answer

      Answer: power = potential difference × current (P = VI)

      Marking points

      • P = VI (power = potential difference × current)
    2. (b)Calculate the current in the cable.

      3 marks
      Show the answer

      Answer: P = 66 000 000 W and V = 132 000 V. I = P ÷ V = 66 000 000 ÷ 132 000 = 500 A.

      Marking points

      • Converting to 66 000 000 W and 132 000 V
      • I = 66 000 000 ÷ 132 000
      • I = 500 A
    3. (c)Calculate the power wasted heating the cable.

      2 marks
      Show the answer

      Answer: P = I²R = 500² × 2.0 = 500 000 W (0.50 MW)

      Marking points

      • P = 500² × 2.0 (allow their current from the part above)
      • P = 500 000 W
    4. (d)The engineers also considered sending the power at 33 kV. Calculate how many times greater the power wasted in the cable would be at 33 kV.

      2 marks
      Show the answer

      Answer: At 33 kV the current would be 66 000 000 ÷ 33 000 = 2000 A, four times as large. The heating would be 2000² × 2.0 = 8 000 000 W, which is 16 times greater.

      Marking points

      • Current at 33 kV = 2000 A (four times as large)
      • Power wasted = 8 000 000 W, so 16 times greater (allow 4² = 16)
  3. 3.Across the country, the National Grid carries energy from where it is generated to where it is used.

    1. (a)Explain the purpose of the step-up and the step-down transformers in the National Grid. Your answer should refer to the current in the cables and to energy transfers.

      6 marks
      Show the answer

      Answer: Step-up transformers at the power station increase the potential difference before the energy is sent along the transmission cables. For the same power, a higher p.d. means a smaller current, because P = VI. The heating of the cables depends on the square of the current (P = I²R), so a smaller current means much less heating. Less energy is dissipated to the surroundings, so a bigger share of the energy from the power station reaches consumers and the system is efficient. Near the consumers, step-down transformers decrease the p.d. to about 230 V, because the transmission p.d. would be far too dangerous in homes. (Level-of-response marking: the whole answer is judged and given a level, not ticked point by point. An answer that links every step in order, like this one, earns the top level.)

      Marking points

      • Step-up transformers raise the p.d. as the power leaves the power station.
      • For the same power, a higher p.d. means a lower current (P = VI).
      • A lower current causes less heating of the cables (heating depends on I², P = I²R).
      • So less energy is dissipated (wasted) to the surroundings, which makes the transfer efficient.
      • Step-down transformers decrease the p.d. (to about 230 V) for use in homes.
      • A very high p.d. would be dangerous in homes (appliances are designed for about 230 V).
  4. 4.A power station sends out 500 MW. In one part of the National Grid, 497 MW of this reaches the substations at the far end of the transmission cables.

    1. (a)Calculate the efficiency of the transmission cables.

      2 marks
      Show the answer

      Answer: efficiency = useful power output ÷ total power input = 497 ÷ 500 = 0.994 (99.4%)

      Marking points

      • efficiency = 497 ÷ 500
      • 0.994 (accept 99.4%)
    2. (b)State what happens to the 3 MW that does not reach the substations.

      1 mark
      Show the answer

      Answer: It heats the cables and is dissipated to the surroundings.

      Marking points

      • It heats the cables (and is dissipated to the surroundings).
    3. (c)The same power is sent along the same cables at a lower potential difference. Explain what happens to the efficiency of the transmission.

      3 marks
      Show the answer

      Answer: The efficiency decreases. At a lower p.d., the current needed for the same power is larger. A larger current heats the cables more, so more energy is wasted.

      Marking points

      • The efficiency decreases.
      • The current is larger (for the same power).
      • More heating of the cables, so more energy is dissipated (wasted).

Quick check

6 questions

  1. 1.What is the National Grid?
  2. 2.Where is a step-up transformer used in the National Grid?
  3. 3.The p.d. used to send a fixed power along a cable is raised from 25 kV to 400 kV. What happens to the current in the cable?
  4. 4.The current in a transmission cable is made three times bigger. What happens to the power wasted heating the cable?
  5. 5.Why is the p.d. stepped down before electricity reaches homes?
  6. 6.Why does sending power at a high p.d. make the National Grid efficient?