What this topic covers
A transformer changes the size of an alternating voltage.
The parts of a transformer (Core)
- The primary coil takes in energy from an a.c. supply.
- The secondary coil passes energy on to the output.
- Both are wound on a soft-iron core.
The coils are insulated wire and are not connected to each other. Soft iron gains and loses its magnetism easily, so the field in the core keeps pace with a reversing current. Transformers are used only with alternating current.
Step-up or step-down? (Core)
Here and are the voltages across the primary (p) and secondary (s) coils, and and are their turns. A step-up transformer has more secondary turns than primary turns, so its output voltage is higher than its input. A step-down transformer has fewer secondary turns and a lower output.
Worked example 1 (Core). A transformer on a pole steps 11 000 V down to 230 V for a street of houses. Its secondary has 46 turns. Find the number of primary turns.
Known values: V, V and . Rearranging the turns equation and substituting:
Answer: 2200 turns.
How a transformer works (Supplement)
- An alternating current flows in the primary coil, so the magnetic field it sets up in the soft-iron core keeps changing in strength and direction.
- The core links this changing field with every turn of the secondary coil.
- A changing field linking a coil induces an e.m.f. across it, so an alternating voltage appears across the secondary.
With a battery, the current and therefore the field stay constant, so nothing is induced except a brief e.m.f. at the instant of switching on or off.
Power and current (Supplement)
For a 100% efficient transformer, power out equals power in:
No energy is created, so stepping the voltage up steps the current down by the same factor. If the pole transformer above supplies 110 A at 230 V, it draws A from the 11 000 V line.
Transmission at high voltage
(Core) Power stations feed their output through a step-up transformer, which raises the voltage before the electricity enters the long-distance cables. Near the users, step-down transformers lower it in stages. Two advantages follow:
- the current in the cables is smaller, so much less energy is wasted heating them
- cables with a smaller cross-section are enough, which saves cost
(Supplement) Cables of resistance waste power , and for a fixed power gives the current.
Worked example 2 (Supplement). A hydroelectric station sends 60 MW through cables with a total resistance of 2.5 Ω. Compare the power wasted at 30 kV and at 300 kV.
At 30 kV, A, so the power lost is W: 10 MW, a sixth of the power sent.
At 300 kV, A, so the power lost is W: 0.10 MW, under 0.2%.
Ten times the voltage cuts the loss by a factor of 100.
Simulation tasks
In the simulation above, 230 V a.c. drives the 1000-turn primary, and the secondary has 50 turns and a 5 Ω lamp.
- (Core) Work out the output from the turns ratio, then check Output voltage: 11.5 V. (Supplement) Input current × 230 V and Output current × 11.5 V both give about 26.5 W, as shown on Power in and Power out.
- (Core) Press Swap: 50 primary and 1000 secondary turns give 4600 V, and a danger warning appears.
- (Supplement) Press Use d.c. with the simulation running (Play starts it if paused). The trace shows one pulse, then the lamp stays dark. Off and then On each give one more pulse.
- (Core) Press Grid: 100 MW leaves the station at 25 kV, and Heating the lines reads 32.0 MW. Press Raise three times, to 400 kV, and the loss drops to 0.125 MW. (Supplement) Confirm it with , using the 250 A in Current in the lines and the 2 Ω line resistance.
The grid voltages in the simulation are UK values. The 0625 syllabus does not ask you to learn any particular grid voltage.