A transformer on the workbench
The first view is a working transformer on a workbench. On the left, an a.c. supply and a switch feed the primary coil, which is wound on one side of a square iron core built from thin sheets. The secondary coil sits on the opposite side and lights a lamp. Sliders set the input voltage, the number of turns on each coil, the lamp's resistance and the efficiency. Along the bottom, a two-channel trace plots the input and the output against time, each on its own scale, while the core glows purple as its magnetic field grows, shrinks and reverses.
How the turns set the output
The current in the primary keeps changing direction, so the field it makes in the core does too. The core guides that changing field round through the secondary coil, and any coil threaded by a changing field has a p.d. induced across it. Each turn of the secondary picks up the same small p.d., and the turns add together, so the two p.d.s are in the same ratio as the turns:
AQA writes the turns as and ; choose your course under Show symbols for to see its own letters. Fewer turns on the secondary steps the p.d. down, and more turns steps it up. Press Swap to exchange the coils and turn one kind into the other.
Power in, power out
No transformer can make energy. An ideal one passes on all the power it takes from the supply, so , and whatever happens to the p.d. happens the opposite way to the current. A transformer stepping 12 V up to 48 V draws four times the lamp's current from its supply. Move the Efficiency slider below 100% to model a real transformer, whose coils and core warm up: the output p.d. still follows the turns, but the supply must provide extra power, shown leaking away as heating in the energy-flow diagram.
Why a battery will not do
Press Use d.c. and the supply becomes a battery. Its steady current makes a steady field: the core still glows, yet nothing in it is changing, so nothing is induced and the lamp stays dark. The trace shows a short pulse only at the instants you switch on or off, while the field builds up or collapses. The electromagnetic induction simulation looks at that effect on its own.
One hundred megawatts across the country
Press Grid for the second view. A power station sends out a steady 100 MW from generators at 25 kV, and you choose the transmission voltage: 25 kV with no step-up, or the UK values of 132 kV, 275 kV and 400 kV. The current in the lines is , and the lines waste by heating up. At 25 kV the current is 4000 A, the lines glow on the stage, about a third of the power is lost and three houses in the town stay dark. At 400 kV the current is only 250 A, sixteen times smaller, so the heating falls by 16 × 16 = 256 times. The bars under the stage compare all four voltages, and the Sankey diagram shows where each second's energy ends up.
Inside the model
The lines have a single total resistance, 2 Ω to start with; real values depend on the length and thickness of the route. The grid's transformers are treated as perfect, and a single step-down transformer stands in for the several stages that bring the voltage down to the mains supply. Other countries choose other values, such as roughly 500 kV and 220 kV in Pakistan. The a.c. is slowed right down so you can follow it, the switching pulses are not to scale, and the moving dots show the size of the current rather than charges racing from the power station to your home.